Technical Specification |
RS 2000 |
Input |
Voltage |
110Vac/140Vac/160Vac-300Vac (Based on load percentage 0%~25% / 25%~50% / 50%~100%) |
Frequency |
45Hz~65Hz |
Phase |
Single Phase with Ground |
Power Factor |
≥ 0.99 (with full linear load) |
Output |
Capacity |
2000VA/1800W |
Voltage |
230V, adjustable to 200/208/220/230/240 |
Voltage Regulation |
≤ ± 1% until low battery warning |
Frequency |
3Hz or 1Hz (selectable) |
Frequency (Battery mode) |
50Hz/60Hz ± 0.1% unless synchronized to line |
Harmonic Distortion |
< 3% (at full load) ; < 6% (at full non-linear load) |
Current Crest Factor |
3:1 (acceptable) |
Waveform |
Pure Sine Wave |
OVERLOAD CAPACITY |
Line mode / Battery mode |
<105% continuous, >106%~120% for 30 seconds transfer to bypass, >121%~150% for 10 seconds transfer to bypass, >150% for immediately transfer to bypass, Buzzer continuously alarms. |
Bypass mode |
<105% continuous, >106%~120% for 250 seconds shuts down, >121%~130% for 125 seconds shuts down, >131%~135% for 50 seconds shuts down, >136%~145% for 20 seconds shuts down, >146%~187% for 5~0.32 seconds shut down, >188% for 0.16 seconds shuts down, Buzzer continuously alarm |
OVERALL EFFICIENCY |
≥ 88% |
INTERNAL BATTERY |
Number of batteries |
4 |
Battery type |
12V/7.2AH (Sealed, non-spillage, maintenance-free, lead acid) |
Rated Battery Voltage |
48Vdc |
Backup time (half load/full load) |
10 ~ 30 minutes depending on loads |
Recharge time (to 80%) |
≤ 5 hours |
Floating Charging Voltage |
54.6Vdc ± 0.5V |
Bulk Charging Voltage |
60.0Vdc ± 0.5V |
TRANSFER TIME |
AC to DC |
0ms |
DC START |
Yes |
SELF DIAGNOSTICS |
By button of the panel or Software Control |
FRONT PANEL |
Standard LED |
Load Level/Battery Level/ Battery Mode/ Normal Mode/ Bypass Mode/ Self-Test/ Weak/Bad Battery/ Site Wiring Fault/ Fault/ Overload |
Optional LED |
Programmable Outlet 1 / Programmable Outlet 2 |
Optional LCD |
Readings: Load Percentage (%), Battery Voltage (V), Input Voltage, Input, Frequency, Output Voltage, Output Frequency, Output Current Icon Indicators: Eco Mode, Utility Mode, Battery Mode, Service Mode, UPS Fault, Overload, UPS Status, UPS Outlets 1&2 |
Button |
ON/Alarm Silence Button / OFF Button / Test/Level Button |
AUDIBLE ALARM |
Battery Mode |
Sounding once every 1.5 seconds |
Low Battery |
Sounding once every 0.2 seconds |
Overload |
Sounding once every 3 seconds Normal alarm |
Normal alarm |
Sounding once every 3 seconds |
Fault |
Continuously Sounding |
PROTECTION |
Short Circuit |
Bypass mode: FUSE, Normal Mode: Output Breaker/Electronic Circuit, Battery Mode: Output Breaker/Electronic circuit |
|
Battery |
Advance Battery Discharge Management |
|
EPO |
UPS shuts down immediately |
|
Over Temperature |
Normal mode: Transfer to Bypass Mode, Battery Mode: UPS shuts down immediately |
PHYSICAL |
Dimensions (H x W x D in mm) |
322 x 152 x 438 |
|
Weight (kg) |
22 |
|
Outlet |
(6) 10A, IEC 320-C13 |
ENVIRONMENT |
Operation Temperature |
0-40°C |
|
Noise Level |
<50dBA |
|
Relative Humidity |
0 to 90% (Without condensation) |
INTERFACE |
Standards |
RS232 port |
|
Optional |
Dry contact, 2nd RS232, USB, SNMP/Web Card |
|
Compatible platforms |
Microsoft Window series, Linux |
STANDARDS AND CERTIFICATIONS |
Safety |
IEC/EN62040-1-1 |
|
Performance |
IEC/EN62040-3 |
|
EMC |
IEC/EN62040-2 class A, FCC Part 15 Subpart B class A, IEC/EN55011, CISPR 11, IEC 61000-4-2/-3/-4/-5, IEC 61000-2-2, IEC 61000-3-2/-3 |
|
Markings |
CE, FCC |