Specifications |
5kVA 1:1 |
6kVA 1:1 |
6kVA 3:1 |
8kVA 1:1 or 3:1 |
11kVA 1:1 or 3:1 |
Rating (kVA/kW) |
5kVA/4.5kW |
6kVA/5.4kW |
6kVA/5.4kW |
8kVA/7.2kW |
11kVA/10kW |
Electrical Characteristics |
Technology |
On-line double conversion with Power Factor Correction (PFC) system |
system |
Input voltage |
200/208/220/230/240V 1:1 |
200/208/220/230/240V/250V 1:1, 380/400/415 3:1 |
Input voltage range |
176-276V without derating (up to 100-276V with derating) 1:1, 305V-480V without derating (up to 175V-480V with derating) 3:1 |
Output voltage/THDU |
200/208/220/230/240V +/– 1%; THDU <2% |
Input frequency range/THDI |
40-70Hz, 50/60Hz autoselection, frequency converter as standard, THDI < 5% |
Efficiency |
Up to 94% in Online mode, 98% in Hi-Efficiency mode |
Short circuit current |
90A |
90A |
90A |
120A |
150A |
Overload capacity |
102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 500ms |
102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 900ms |
Connections |
Input |
Terminal block (up to 10 mm2 ) |
Terminal block (up to 16mm2 ) |
Outputs |
Terminal block + 2 controlled groups of 4 IEC C13 (10A) + 2 IEC C19 (16A) |
Terminal block |
Outputs with HotSwap Maintenance Bypass |
Terminal block + 3 IEC C13 (10A) + 2 IEC C19 (16A) |
Terminal block + 4 IEC C19 (16A) |
Batteries |
Typical backup times at 50 and 70% load* |
9PX |
13/10 min |
11/8 min |
30/20min |
20/15 min |
13/9min |
9PX + 1 EBM |
60/40 min |
48/34 min |
70/45min |
48/32 min |
32/21 min |
9PX + 4 EBM |
220/150 min |
170/120 min |
210/140 min |
140/100 min |
100/70 min |
Battery management |
ABM® and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units. |
Communication |
Communication ports |
1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal block for remote On/Off and 1 for remote power Off, 1 DB15 for parallel operation. |
Communication slot |
1 slot for Network-MS card, ModBus-MS or Relay-MS cards |
Operating conditions, standards and approvals |
Operating temperature |
0 to 40°C continuous |
Noise leve |
<45dB |
<45dB |
<48db |
<48db |
<50db |
Safety |
IEC/EN 62040-1, UL 1778 (1:1 version) |
EMC, performance |
IEC/EN 62040 -2, FCC Class A (1:1 version), IEC/EN 62040-3 (Performance) |
Approvals |
CE, CB report (TUV), UL (1:1 version) |
Dimensions H x W x D/Weight |
UPS Dimensions |
440(19’’)*130(3U)*685mm |
440(19’’)*130(3U)*685mm |
440(19’’)*260(3U+3U)*700mm |
440(19’’)*260(3U+3U)*700mm |
440(19’’)*260(3U+3U)*700mm |
UPS Weight |
48kg |
48kg |
88kg |
84kg (1:1), 88kg (3:1) |
86kg (1:1), 88kg (3:1) |
EBM Dimensions |
440(19’’)*130(3U)*645mm |
440(19’’)*130(3U)*645mm |
440(19’’)*130(3U)*680mm |
440(19’’)*130(3U)*680mm |
440(19’’)*130(3U)*680mm |
EBM Weight |
68kg |
68kg |
65kg |
65kg |
65kg |
Power Module Dimensions |
|
|
440(19’’)*130(3U)*700mm |
440(19’’)*130(3U)*700mm |
440(19’’)*130(3U)*700mm |
Power Module Weight |
|
|
23kg |
19kg (1:1), 23kg (3:1) |
21kg (1:1), 23kg (3:1) |